50/51 | instantaneous/definite-time, three-stages, three-phase overcurrent protection |
51 | overcurrent, inverse-time |
50N/51N | ground overcurrent, definite-time, two-stages protection |
51N | ground overcurrent, inverse-time |
49M | thermal overload, inverse-time current protection |
49R | thermal overload, inverse-time current protection |
46 | negative-sequence overcurrent protection, definite-time and inverse-time |
46G | negative-sequence overcurrent protection, inverse-time |
62 | external protection |
The energising values are input current: IL1, IL2, IL3 and I0. On the basis of measured currents, the negative-sequence current I2 is calculated, which is the measure of current unbalance. Exceeding of any set threshold value causes the reaction of the relay according to the configuration. Communication interface provides following data: current measured and calculated values of voltages and their phase shifts, current inputs and outputs statuses, relay outputs states and registered runs. Software provided with the relay allows to: relay configuration, reading and writing settings, picked-up signals quitting, graphic preview of measured values and registered records preview.
Rated measuring current In | 1A, 5A |
Rated frequency | 50Hz |
Auxilliary voltage Upn | 24V DC, od 48V do 60V DC, 110V DC/AC, 230V DC/AC |
Control voltage | acc. to aux voltage |
Setting range of current threshold values | |
50/51 protection functions | 0,2…30In |
50N/51N def.time protection functions | 5…500mA or 5…5000mA |
50N/51N inv.time protection functions | 5…100mA or 5…1000mA |
51 inv. time char. A, B, C | 0,2…2 In |
49R thermal char. | 0,5…1,5Ib |
46 protection function | 0,1…1 In |
46G protection function | 0,1…0,5 Ib |
Base current Ib setting range: | |
49R protection function | 0,1…2,5 In |
49M protection function | 0,2…1,2 In |
46G protection function | 0,5…2,5 In |
Setting range of tripped currents counter | (1÷ 65000)In |
Setting range of operating time | |
definite-time operating characteristics | 0…99,9s |
according to A, B, C characteristics defined by EN60255-3 regulation | |
according to 49M protection function characteristic, defined by EN-60255-8 regulation | |
Relay response time for current protection functions | ≤40ms |
Accuracy of current inputs | 2,5% |
Accuracy of time measuring | 1%÷10ms |
Burden in measuring inputs | ≤0,5VA/input |
Burden of supply module | ≤5W |
Continuous measured current | 4In |
Thermal withstand (1s) | 80In |
Dynamic withstand | 200In |
Relay outputs data: | |
Max. breaking capacity by 250V DC | |
resistive load | 0,3A |
inductive load of L/R ≤40ms | 0,1A |
Max. breaking capacity by 250V, 50Hz | |
inductive load, cosϕ=0,4 | 3A |
Continuous contact carry | 6A |
Amient temperature | (253÷328)K/(-20÷55)°C |
Relative humidity | ≤80% |
Ingress Protection degree | P40 |
Weight | ~0,8kg |
Dimensions (height x width x depth | 75 x 100 x 120 mm |
Electromagnetic compatibility according to | PN-EN 60255-26 |
Insulation according to | PN-EN 60255-5 |