50/51 | instantenoues/definite-time, two-stages, three-phase overcurrent protection |
50N/51N | ground overcurrent, definite-time, two-stages protection (ver. A) |
49M | thermal overload, inverse-time current protection |
51LR | overcurrent, against motor stall |
51LR | overcurrent, against locked rotor |
38 | temperature-based (PTC-sensors) (ver. B |
37 | undercurrent, against motor idle |
48/66 | motor start-up supervision |
46 | current unbalance protection (negative-sequence overcurrent) |
59/27 | under-/overvoltage, definite-time, two-stages (ver. C) |
62 | external protection |
On the basis of three measured phase currents, the negative-sequence of current is calculated which is the value of current unbalance. Exceeding of any set threshold value causes the reaction of the relay according to the configuration. Communication interface provides measured and calculated electrical values, binary inputs and outputs states and saved records. The manufacturer provides PC software allowing to set the relay, confirm signals, graphical display of measured values and browse records.
Rated measuring current In | 1A or 5A |
Rated measuring voltage Un | 100V |
Rated frequency | 50Hz |
Auxilliary voltage | 24V DC, od 48V do 60V DC, 110V DC/AC, 230V DC/AC |
Control voltage | acc. to aux voltage |
Setting ranges of current threshold values | |
– 50/51 protection functions | (0,2÷30) In |
– 50N/51N def.time protection functions | (5÷500)mA or (5 ÷ 5000)mA |
– 46 protection function | (0,1÷1) In |
Base current Ib setting range: | |
– 51LR (locked rotor) function | (0,1÷2,5) In |
– 49M, 51LR (motor stall), 48/66 protection functions | (0,2÷1,2) In |
Setting range of temperature threshold value | ϑ =(40 ÷ 200)°C |
Setting range of voltage threshold value | (0,05 ÷ 1,20) Un |
Setting range of operating time | |
– definite-time operating characteristics | (0÷99,9)s |
– according to 49M protection function characteristic, defined by EN-60255-8 standard |
|
Relay response time for 50/51 protection functions | ≤40ms |
Accuracy of current inputs (if I=In) | 2,5% |
Accuracy of voltage inputs (if U=Un) | 1% |
Accuracy of time measuring | 1% ± 10ms |
Burden in measuring inputs | ≤0,5VA/input |
Burden of supply module | ≤5W |
Continous measured current | 4In |
Thermal withstand (1s) | 80In |
Dynamic withstand | 200In |
Relay outputs data: | |
Max. breaking capacity by 250V DC | |
– resistive load | 0,3A |
– inductive load of L/R ≤40ms | 0,1A |
Max. breaking capacity by 250V, 50Hz | |
– inductive load, cosϕ=0,4 | 3A |
Continuous contact carry | 6A |
Ambient temperature | (253÷328)K/(-20÷55)°C |
relative humidity | ≤80% |
Ingress Protection degree | IP40 |
Weight | ~0,7kg |
Dimensions (height x width x depth) | 75 x 100 x 120 mm |
Electromagnetic compatibility acc. to | PN-EN 60255-26 |
Insulation according to | PN-EN 60255-5 |