76 | overcurrent (AVR), time-delayed, two-stages |
50/51 | overcurrent (RMS), time-delayed, two-stages |
59 | overvoltage (AVR), two-stages |
59 | overvoltage (RMS), two-stages |
27 | undervoltage (AVR), two-stages |
62 | external protection |
SMiS software provided with each device allows to: protection functions configuration, read and write of protection settings, acknowledgment of relay pick-up signal and browsing relay recorded data.
Rated measuring current Idcn | Idcn=1A or Idcn=5A |
Rated measuring voltage Udcn | 100V |
Auxilliary voltage | (24V, 48V/60V)DC, (110V, 230V)DC/AC |
Control voltage | acc. to aux voltage |
Setting ranges of threshold values: | |
– current threshold value | (0,20÷20,00) Idcn or (0,05÷5,00) Idcn |
– voltage threshold value | (0,05÷1,20) Udcn |
– operating time | (0,00÷99,99)s |
Relay operation time for current protection | <30ms |
Relay operation time for voltage protection | <100ms |
Accuracy of current inputs if I=IDCn | 1% |
Accuracy of voltage input if U=UDCn | 0,5% |
Accuracy of time measuring | 1% ±10ms |
Burden in current measuring inputs | ≤0,5W |
Burden in voltage measuring inputs | ≤1W |
Burden of supply module | ≤6W |
Continuous measured current | 4Idcn |
Thermal withstand (1s) | 80Idcn |
Dynamic withstand | 200Idcn |
Continuous measured voltage | 1,2Udcn |
Thermal withstand (10s) | 1,5Udcn |
Relay outputs data: | |
Max. breaking capacity by 250V DC | |
– resistive load | 0,3A |
– inductive load of L/R ≤40ms | 0,1A |
Max. breaking capacity by 250V, 50Hz | |
– inductive load, cosϕ=0,4 | 3A |
Continuous contact carry | 6A |
Ambient temperature (operation) | (253÷328)K/(-20÷55)°C |
Ambient temperature (storage) | (248÷343)K/(-25÷70)°C |
Relative humidity | ≤80% |
Ingress Protection degree | IP40 |
Weight | ~0,7kg |
Dimensions (height x width x depth) | 75 x 100 x 120 mm |
Electromagnetic compatibility according to | EN 60255-26 |
Insulation according to | EN 60255-27 |