50/51 | instantenoues/definite-time, three-stages, three-phase overcurrent protection |
49R | thermal overload, inverse-time current protection |
46 | current unbalance protection |
67N | directional ground overcurrent protection |
59N | residual overvoltage protection |
50N/51N | ground overcurrent, definite-time, two-stages protection |
51N | ground overcurrent, inverse-time protection |
62 | external protection |
Communication interface provides measured and calculated electrical values, binary inputs and outputs states and saved records. The manufacturer provides PC software allowing to set the relay, confirm signals, graphical display of measured values and browse records.
Rated measuring current | 5A |
Rated measuring voltage | 100V |
Rated frequency | 50Hz |
Auxilliary voltage | 24V DC, 48V – 60V DC, 110V DC/AC, 230V DC/AC |
Control voltage | acc. to aux voltage |
Setting range of threshold value of voltage in 59N protection | (0,05÷1,20)Uon |
Setting range of current threshold values | |
(0,2÷30)In for | „50/51” def. time |
(5÷500)mA or (50÷5000)mA for | „50N/51N” def. time |
(5÷100)mA or (50÷1000)mA for | „50N/51N” inv. time |
(0,5÷1,5)Ib for „49R” protection | |
(0,1÷1)In for „46” protection | |
Base current Ib setting range | (0,1÷2,5)In |
Setting range of 67N protection function | |
– current threshold value | (5÷100)mA or (0,05÷1,00)A |
– voltage threshold value | (0,01÷0,99)Uon |
– characretistic angle | (0÷90)° – cap. |
Setting range of sum of tripped currents counter | (1÷ 65000)In |
Setting range of operating time | |
– definite-time operating characteristics | (0÷99,9)s |
– according to 49R protection function characteristic | |
Relay response time for 50/51 protection functions | ≤40ms |
Relay response time for ground protection functions | ≤100ms |
Accuracy of voltage inputs | 0,5% if Uo=Uon |
Accuracy of current inputs | 1% if I=In |
Accuracy of time measuring | 1% ± 10ms |
Burden in measuring inputs | ≤0,5VA/input |
Burden of supply module | ≤6W |
Thermal/dynamic withstand of current inputs | 80In /250In |
Continuous/thermal withstand of voltage inputs | 1,2 Uon/1,44 Uon |
Relay outputs data: | |
Max. breaking capacity by 250V DC | |
– resistive load | 0,3A |
– inductive load of L/R ≤40ms | 0,1A |
Max. breaking capacity by 250V, 50Hz | |
– inductive load, cosϕ=0,4 | 3A |
Continuous contact carry | 6A |
Ambient temperature | (253÷328)K/(-20÷55)°C |
Relative humidity | ≤80% |
Ingress Protection degree | IP40 |
Weight | ~0,8kg |
Dimensions (height x width x depth) | 75 x 100 x 120 mm |
Electromagnetic compatibility according to | PN-EN 60255-26 |
Insulation according to | PN-EN 60255-5 |