27/59 | Under-/overvoltage, definite-time, three-stages, three-phase (OR/AND operation mode) |
59N | Residual overvoltage, three-stages |
47 | Negative-sequence overvoltage, two-stages |
27D | Positive-sequence overvoltage, two-stages |
27S/59S | Rate of change of voltage by voltage derivative |
27SA | Rate of change of voltage by average voltage change |
27I/59I | Voltage integral based |
62 | External protections |
The energizing values are input voltages: UL1, UL2, UL3 and U0 if Un=100V or UL1, UL2, UL3 if Un=100V. On the basis of measured voltages other energizing values are calculated: positive-sequence voltage U1, negative-sequence voltage U2, derivative of voltage, rate of change of voltage, integral of voltage. Exceeding of any set threshold value causes the reaction of the relay according to the configuration. Communication interface provides measured and calculated electrical values, binary inputs and outputs states and saved records. The manufacturer provides PC software allowing to set the relay, confirm signals, graphical display of measured values and browse records.
Rated measuring voltage Un | 100V 400V |
Rated frequency fn | 50Hz |
Auxilliary voltage | 24V DC, 48V – 60V DC, 110V DC/AC, 230V DC/AC |
Control voltage | acc. to aux voltage |
Setting ranges of protections treshold values: | Ur = (0,05÷1,2)Un for „27 / 27D / 47 / 59 / 59N” dUr = (-1,00÷-0,01)1/s or (0,01÷1,00)1/s for „(27S / 59S)” DUr = (-0,100÷-0,003)1/s or (0,003÷0,100)1/s for „(27SA / 59SA)” CUr = (0,01÷2,00) for „27I / 59I” |
Setting range of timer | (0÷99,9)s |
Pick-up time for „27 / 27D / 47 / 59” | ≤40ms |
Pick-up time for „59N / 27S / 59S” | ≤100ms |
Pick-up time for „27SA / 59SA / 27I / 59I” | ≤(1,00 ÷ 30,00)s + 40ms |
Accuracy of voltage measuring | δ ≤0,5% for U=(0,7 ÷ 1,3)Un δ ≤1% for U=(0,3 ÷ 0,7)Un δ ≤2,5% for U=(0,05 ÷ 0,3)Un δ ≤5% in the rest of measuring range |
Accuracy of time measuring | ± 10ms |
Burden in measuring inputs | ≤0,5VA/input if U=Un |
Burden of supply module | ≤5W |
Continuous measured voltage | 1,2Un (1,2Uon) |
Thermal withstand (10s) | 1,44Un (1,44Uon) |
Relay outputs data: | |
Max. breaking capacity by 250V DC | |
– resistive load | 0,3A |
– inductive load of L/R ≤40ms | 0,1A |
Max. breaking capacity by 250V, 50Hz | |
– inductive load, cosϕ=0,4 | 3A |
Continuous contact carry | 6A |
Ambient temperature | (253÷328)K/(-20÷55)°C |
Relative humidity | ≤80% |
Ingress Protection degree | IP40 |
Weight | ~ 0,7kg |
Dimensions (height x width x depth) | 75 x 100 x 120 mm |
Electromagnetic compatibility acc. to | EN 60255-26 |
Insulation according to | PN-EN 60255-5 |