50N/51N | ground overcurrent, instantenous or definite-time |
RioT-400 protection relay supervises the magnitude of measured current and compares it to threshold value set by the user. When measured value exceeds threshold value, relay picks-up and after set time delay, activates operation signal. Operation of the relay can be blocked by energising blocking binary input Ubl.
Rated measuring current I0n | 5A |
Rated frequency | 50Hz |
Auxilliary voltage | 24V DC, 48V – 60V DC, 110V – 230V DC/AC |
Setting range of current threshold value | (5÷99,9)mA for RIoT-400-05 or (50÷999)mA for RIoT-400-50 or (0,5÷4,99)A for RIoT-400-500 |
Accuracy of current input | 2,5% |
Relay response time | ≤100ms |
Setting range of timer | (0÷9,9)s |
Burden in measuring input | ≤0,5VA |
Burden in supply module | ≤6W |
Continuous measured current | 2,2In |
Thermal withstand (1s) | 80In |
Dynamic withstand | 200In |
Relay outputs data: | |
Max. breaking capacity by 250V DC | |
– resistive load | 0,3A |
– inductive load of L/R ≤40ms | 0,12A |
Max. breaking capacity by 250V, 50Hz | |
– inductive load, cosϕ=0,4 | 3A |
Continuous contact carry | 5A |
Ambient temperature | (268÷313)K/(-5÷40)°C |
Humidity (with no condensation) | ≤80% |
Ingress Protection degree | IP40 |
Weight | 0,7kg |
Dimensions (height x width x depth) | 75 x 100 x 120 mm |
Electromagnetic compatibility according to | PN-EN 50263 |
Insulation according to | PN-EN 60255-5 |