51 | overcurrent, definite-time characteristic |
RIT-430A controls the RMS values of measuring currents, selects the maximum value and compares it with setting value of current, which is set by user. If one of measured values exceeds the setting value, the relay pick-ups and after set time-delay, the trip signal is generated. Operation of relay is blocked when blocking input (Ubl) is energised.
Rated current In | 1A, 5A, 1A or 5A |
Rated frequency fn | 24V DC, 48V – 60V DC, 110V – 230V DC/AC |
Setting range of threshold current | (0,05÷5)In or (0,2÷20)In |
Accuracy of current input | 2,5% |
Pick-up time | ≤40ms |
Setting range of timer | (0÷99,9)s |
Burden of analog inputs | ≤0,5VA/input |
Burden of auxilliary voltage supply | ≤6W |
Continous thermal withstand of current input | 2,2In |
1 sec thermal withstand of current input | 80In |
Dynamic withstand of current inputs | 200In |
Relay outputs data (K1, K2, K3) | |
Max. breaking capacity by U=250V DC | |
– resistive load | 0,3A |
– inductive load of L/R=40ms | 0,12A |
Max. breaking capacity by U=250V, 50Hz | |
– inductive load of cosϕ=0,4 | 3A |
Continuous contact carry | 5A |
Relay outputs data (K4, K5) | |
Max. breaking capacity by resistive load | |
– AC current | 6A |
– DC current | 6A/28V; 0,16A/220V |
Continuous contact carry | 5A |
Ambient temperature | (268÷313)K/(-5÷40)°C |
Relative humidity | ≤ 80% |
Igress Protection degree | IP40 |
Weight | 0,8kg |
Dimensions (width x hight x depth) | 75 x 100 x 120 mm |
Electromagnetic compatibility according to | PN-EN 50263 |
Insulation according to | PN-EN 60255-5 |