50/51 | instantenoues/definite-time, three-stages, three-phase overcurrent protection |
51 | inverse-time overcurrent protection |
50N/51N | ground overcurrent, definite-time, two-stages protection |
51N | ground overcurrent, inverse-time protection |
21N | admittance-based ground fault protection |
67N | directional ground overcurrent protection |
59N | residual overvoltage protection |
62 | external protection |
79 | auto-reclose automation |
Communication interface provides measured and calculated electrical values, binary inputs and outputs states and saved records. The manufacturer provides PC software allowing to set the relay, confirm signals, graphical display of measured values and browse records.
Rated measuring current In | 5A |
Rated measuring voltage | 100V |
Rated frequency | 50Hz |
Auxilliary voltage | 24V DC, od 48V do 60V DC, 110V DC/AC, 230V, DC/AC |
Control voltage | acc. to aux voltage |
Setting range of threshold value of voltage in 59N protection | 0,05…1,20 Uon |
Setting range of current threshold values | |
– 50/51 protection functions | 0,2…30 In |
– 50N/51N def.time protection functions | 5…500mA or 50…5000mA |
– 50N/51N inv. time protection functions | 5…100mA or 50…1000mA |
Setting range of 67N protection function | |
– current threshold value | 5…100mA or 0,05…1,00A |
– voltage threshold value | 0,01…0,99 Uon |
– characteristic angle | 0…90° – cap. |
Setting range of 21N protection function | |
– admittance threshold value | 0,05…50,00mS or 0,5…500mS |
– voltage threshold value | 0,01…0,99 Uon |
– characteristic angle | 0…90° – cap. |
– direction | from the busbars to the busbars undirectional |
Setting range of sum of tripped currents counter | 1…65000 In |
Setting range of operating time | 0…99,9s |
Relay response time for 50/51 protection functions | ≤40ms |
Relay response time for ground protection functions | ≤100ms |
Accuracy of current inputs | 1% |
Accuracy of voltage input | 0,5% |
Accuracy of time measuring | 1% ±10ms |
Burden in measuring inputs | ≤0,5VA/input |
Burden in supply module | ≤6W |
Thermal/dynamic withstand of current inputs | 80In /250In |
Continuous/thermal withstand of voltage input | 1,2 Uon/1,44 Uon |
Relay outputs data: | |
Max. breaking capacity by 250V DC | |
– resistive load | 0,3A |
– inductive load of L/R ≤40ms | 0,1A |
Max. breaking capacity by 250V, 50Hz | |
– inductive load, cosϕ=0,4 | 3A |
Continuous contact carry | 6A |
Ambient temperature | (253÷328)K/(-20÷55)°C |
Relative humidity | ≤80% |
Ingress Protection degree | IP40 |
Weight | ~0,8kg |
Dimensions (height x width x depth) | 75 x 100 x 120 mm |
Electromagnetic compatibility acc. to | PN-EN 60255-26 |
Insulation according to | PN-EN 60255-5 |