27/59 | under-/overvoltage, definite-time, three stage, three phase protection (AND/OR operation mode settable) |
59N | residual overvoltage protection, three stages |
47 | negative-sequence overvoltage, two stages |
27D | positive-sequence undervoltage, two stages |
81 | under-/overfrequency, instantenuous or definite-time, five stages |
62 | cooperation with external protection |
Energising values are measured input voltages: UL1, UL2, UL3, U0 and calculated values of positive-sequence of three phase voltage (U1), negative-sequence of three phase voltage (U2) and frequency. If one of measured or calculated values exceed the threshold value set by the user, the relay operates according to configuration.
Communication interface provides measured and calculated electrical values, binary inputs and outputs states and saved records. The manufacturer provides PC software allowing to set the relay, confirm signals, graphical display of measured values and browse records.
Rated measuring voltage Un | 100V or 400V |
Rated frequency fn | 50Hz |
Auxilliary voltage | 24V DC, 48V – 60V DC, 110V DC/AC, 230V DC/AC |
Control voltage | acc. to aux voltage |
Setting range of threshold values of voltage for 27/27D/47/59 protection functions | (0,05÷1,2) Un |
Setting range of threshold value of frequency protections | (40,0 ÷ 65,0)Hz |
Setting range of operating time | (0,00 ÷ 99,99)s |
Number of underfrequency stages to pick-up UFLS automation | 1 ÷ 4 |
Number of overfrequency stages to pick-up Load Restoration after UFLS | 1 |
Relay response time for „27 / 27D / 47 / 59” protection functions | ≤40ms |
Relay response time for „59N” protection functions | ≤100ms |
Accuracy of voltage measuring | δ ≤0,5% if U=(0,7 ÷ 1,3) Un δ ≤1% if U=(0,3 ÷ 0,7) Un δ ≤2,5% if U=(0,05 ÷ 0,3) Un δ ≤5% in the rest of measuring range |
Accuracy of frequency measuring | ± 0,01Hz |
Accuracy of time measuring | 1% ±10ms |
Burden in measuring inputs | ≤0,5VA/input |
Burden of supply module | ≤5W |
Thermal withstand of valtage inputs | |
– continuous | 1,2 Un (1,2 U0n) |
– short-term (10s) | 1,44 Un (1,44 U0n) |
Relay outputs data: | |
Max. breaking capacity by 250V DC | |
– resistive load | 0,3A |
– inductive load of L/R ≤40ms | 0,1A |
Max. breaking capacity by 250V, 50Hz | |
– inductive load, cosϕ=0,4 | 3A |
Continuous contact carry | 6A |
Ambient temperature | (253÷328)K/(-20÷55)°C |
Relative humidity | ≤80% |
Ingress Protection degree | IP40 |
Weight | ~0,7kg |
Dimensions (height x width x depth) | 75 x 100 x 120mm |
Electromagnetic compatibility according to | EN 60255-26 |
Insulation according to | EN 60255-5 |