27/59 | Under-/overvoltage, time-delayed |
27/59 | Under-/overvoltage, instanteneous |
RET-325
The relay supervises the value of measured voltage. If operation mode is set to „overvoltage”, the relay picks-up when measured voltage exceeds the treshold value. After preset time delay, trip (operation) signal is activated. If operation mode is set to „undervoltage”, the relay picks-up when measured voltage drops below the treshold value. After preset time delay, trip (operation) signal is activated.
RET-350
The relay supervises the value of measured voltage. If operation mode is set to „overvoltage”, the relay picks-up and instantenously generates trip (operation) signal when measured voltage exceeds the treshold value. If operation mode is set to „undervoltage”, the relay picks-up and instantenously generates trip (operation) signal when measured voltage drops below the treshold value.
Rated measuring voltage Un | 48V, 100V, 110V, 220/230V, 400V AC/DC |
Rated frequency | 50Hz |
Auxilliary voltage | 110V – 230V DC/AC (50Hz) |
Setting range of voltage threshold values | (1 ÷ 99)V for Un=48V (2 ÷ 198)V for Un=100V (3 ÷ 297)V for Un=110V (4 ÷ 396)V for Un=220/230V (5 ÷ 495)V for Un=400V |
Accuracy of voltage inputs | 1,5% |
Relay response time: | ≤100ms |
Setting range of timer (RET-325) | (0÷9,9)s |
Burden in measuring inputs | ≤0,5VA/input |
Burden in supply module | ≤4W |
Continuous measured voltage | 1,2Un |
Thermal withstand of voltage measuring inputs (10s) | 1,5Un |
Relay outputs data: | |
Max. breaking capacity by 250V DC | |
– resistive load | 0,3A |
– inductive load of L/R ≤40ms | 0,12A |
Max. breaking capacity by 250V, 50Hz | |
– inductive load, cosϕ=0,4 | 3A |
Continuous contact carry | 5A |
Ambient temperature | (268÷313)K/(-5÷40)°C |
Relative humidity | ≤80% |
Ingress Protection degree | IP40 |
Weight | |
RET-325 | 0,35kg |
RET-350 | 0,3kg |
Dimensions (height x width x depth) | 75 x 45 x 130 mm |
Electromagnetic compatibility according to | PN-EN 50263 |
Insulation according to | PN-EN-60255-5 |