ZEG
loader
RET-325/REt-350

Produkty

RET-325/REt-350
Voltage relays
Voltage relays dedicated to supervise the RMS value of sinewaved voltage of frequency 50 Hz or DC voltage. Relays construction ensures their high accuracy, stability and reliabilty.

Manuals, diagrams, technical details

DOWNLOAD FILES

Product description

Protection set of RET-325

27/59 Under-/overvoltage, time-delayed

Protection set of REt-350

27/59 Under-/overvoltage, instanteneous

Main features

  • two-inputs measuring circuit based on voltage divider – for sine voltage (UAC) or direct voltage (UDC)
  • Undervoltage or overvoltage operation mode (selectable)
  • Optical visualisation (LED diodes) of pick-up, operation of relay or auxilliary voltage presence
  • Relay outputs of pick-up signalling (K1) or operation signalling (K2) – RET-325
  • 2 relay outputs of operation signalling (K1, K2) – RET-350
  • 35 mm rail mounting

RET-325

The relay supervises the value of measured voltage. If operation mode is set to „overvoltage”, the relay picks-up when measured voltage exceeds the treshold value. After preset time delay, trip (operation) signal is activated. If operation mode is set to „undervoltage”, the relay picks-up when measured voltage drops below the treshold value. After preset time delay, trip (operation) signal is activated.

RET-350

The relay supervises the value of measured voltage. If operation mode is set to „overvoltage”, the relay picks-up and instantenously generates trip (operation) signal when measured voltage exceeds the treshold value. If operation mode is set to „undervoltage”, the relay picks-up and instantenously generates trip (operation) signal when measured voltage drops below the treshold value.

TECHNICAL DATA

Rated measuring voltage Un 48V, 100V, 110V,
220/230V, 400V AC/DC
Rated frequency 50Hz
Auxilliary voltage 110V – 230V DC/AC
(50Hz)
Setting range of voltage threshold values (1 ÷ 99)V for Un=48V
(2 ÷ 198)V for Un=100V
(3 ÷ 297)V for Un=110V
(4 ÷ 396)V for Un=220/230V
(5 ÷ 495)V for Un=400V
Accuracy of voltage inputs 1,5%
Relay response time: ≤100ms
Setting range of timer (RET-325) (0÷9,9)s
Burden in measuring inputs ≤0,5VA/input
Burden in supply module ≤4W
Continuous measured voltage 1,2Un
Thermal withstand of voltage measuring inputs (10s) 1,5Un
Relay outputs data:
Max. breaking capacity by 250V DC
– resistive load 0,3A
– inductive load of L/R ≤40ms 0,12A
Max. breaking capacity by 250V, 50Hz
– inductive load, cosϕ=0,4 3A
Continuous contact carry 5A
Ambient temperature (268÷313)K/(-5÷40)°C
Relative humidity ≤80%
Ingress Protection degree IP40
Weight
RET-325 0,35kg
RET-350 0,3kg
Dimensions (height x width x depth) 75 x 45 x 130 mm
Electromagnetic compatibility according to PN-EN 50263
Insulation according to PN-EN-60255-5