27 | undervoltage, time-delayed (RET-425P) |
59 | overvoltage, time-delayed (RET-425N) |
RET-425 relay controls the RMS value of input voltage and compares it with setting value. The operation mode depands on type of relay. In overvoltage type (RET-425N), when RMS value of measured voltage exceeds the setting value, pick-up signal is generated and after set time-delay, trip contact closes. The undervoltage type (RET-435P) generates pick-up and trip when measured value drops below setting value.
Rated voltage Un | 100V or 220/230V AC/DC |
Rated frequency fn | 50Hz |
Rated auxilliary voltage Up | 24V DC, 48V – 60V DC, 110V – 230V DC/AC |
Burden of analog inputs | ≤0,5VA/input |
Burden of auxilliary voltage supply | ≤3W |
Setting range of threshold voltage | (10÷200)V for Un=100V (15÷300)V for Un=220/230V |
Accuracy of voltage input | 1,5% |
Relay pick-up time | ≤60ms |
Setting range of timer | (0÷99,9)s |
Continously voltage withstand of voltage inputs | 1,2 Urmax |
10 sec voltage withstand of voltage inputs | 1,4 Urmax |
Relay outputs data | |
Max. breaking capacity by U=250V, DC | |
– resistive load | 0,3A |
– inductive load by L/R=40ms | 0,12A |
Max. breaking capacity by U=250V, 50Hz | |
– inductive load of cosϕ=0,4 | 3A |
Continuous contact carry | 5A |
Ambient temperature | (268÷313)K/(-5÷40)°C |
Relative humidity | ≤ 80% |
Ingress Protection degree | IP40 |
Weight | 0,3kg |
Dimensions (height x width x depth) | 75 x 45x 120 mm |
Electromagnetic compatibility according to | PN-EN 50263 |
Insulation according to | PN-EN 60255-5 |