51 | overcurrent, definite-time |
RIT-433A relay compares the maximum value of three measured currents with threshold values of particular overcurrent stages whose are set by the user. If the RMS value of any of measured currents exceed threshold value of one of overcurrent stages, relay picks-up and after set time, operates. Relay operation signal can be blocked by energising blocking purpose binary input (Ubl). Execution circuit is realised by three relay outputs: K1, K2, K3. Relay output K1 activates if I or II stage operate with adequate time-delay, relay output K2 is instantaneously activated by II stage pick-up, relay output K3 activates when III overcurrent stage operates after its time-delay expires.
Rated measuring current In |
1A, 5A, 1A or 5A |
Rated frequency | 50Hz |
Auxilliary voltage | 24V DC, 48V – 60V DC, 110V – 230V DC/AC |
Setting range of current threshold value | (0,05÷5)In or (0,2÷20)In |
Accuracy of current inputs | 2,5% |
Relay response time | ≤40ms |
Setting range of operating time | (0÷99,9)s |
Burden in measuring inputs | ≤0,5VA/input |
Burden of supply module | ≤6W |
Continuous measured current | 2,2In |
Thermal withstand (1s) | 80In |
Dynamic withstand | 200In |
Relay outputs data (K1, K2, K3): | |
Max. breaking capacity by 250V DC | |
– resistive load | 0,3A |
– inductive load of L/R ≤40ms | 0,12A |
Max. breaking capacity by 250V, 50Hz | |
– inductive load, cosϕ=0,4 | 3A |
Continuous contact carry | 5A |
Relay outputs data (K4, K5): | |
Max. breaking capacity by resistive load | |
– AC current | 6A |
– DC current | 6A/28V; 0,16A/220V |
Continuous contact carry | 5A |
Ambient temperature | (268÷313)K/(-5÷40)°C |
Relative humidity | ≤80% |
Ingress Protection degree | IP40 |
Weight | 0,8kg |
Dimensions (height x width x depth) | 75 x 100 x 120 mm |
Electromagnetic compatibility according to | PN-EN 50263 |
Insulation according to | PN-EN 60255-5 |