50/51 | instantaneous or definite-time overcurrent protection |
50N/51N | instantaneous or definite-time ground overcurrent protection |
49/51 | inverse time overcurrent or thermal overcurrent protection |
46 | negative-sequence overcurrent protection |
The energising values are currents (IL1, IL2, IL3, and I0). On the basis of three phase currents the negative-sequence component I2 is calulated, which indicates the current unbalance. If any of measured values exceeds setting value (set by user), the relay operates in a manner dependind on configuration.
With optional communication interface, the measured currents, binary inputs or outputs, register logs are provided. The PC software provided with relay allows to set the relay, confirm generated signals, graphical display of measured values and browse the register records.
Rated current In | 1A or 5A |
Rated frequency fn | 50Hz |
Rated auxilliary voltage Up | 24V DC, 48V – 60V DC, 110V – 230V DC/AC |
Control voltage Us | acc. do aux. voltage |
Setting range of threshold current | |
(0,2÷20)In for „49/50/51” protection function if def.-time char. set | |
(5÷500)mA or (0,05÷5,00)A – for „50N/51N” protection function if def.-time char. set | |
(0,2÷2)In for „49/51” protection functions if inv. time char.: A, B, C set | |
(0,5÷1,5)Ib dla for „49/51” protection function if 49R char. set | |
(0,1÷1)In for „46” protection function if inv.-time char. A, B, C set | |
(0,1÷0,5)Ib for „46” protection function if inv.time char 46G set | |
Setting range of base current Ib | |
(0,1÷2,5)In for „49/51” protection function if 49R char. set | |
(0,2÷1,2)In for „49/51” protection function if 49M char. set | |
(0,5÷2,5)In for „46” protection function if 49G char. set | |
Accuracy of current input | 2,5% |
Setting range of sum of tripped currents counter limit | (100÷65000)In |
Setting range of timer: | |
|
|
|
|
|
|
Pick-up time | ≤40ms |
Burden in analog inputs | ≤0,5VA/input |
Burden in auxilliary voltage supply | ≤6W |
Continous thermal withstand of current input | 2,2In |
1 sec thermal withstand of current input | 80In |
Dynamic withstand of current input | 200In |
Relay outputs data (S2 – S5) | |
Max. breaking capacity by U=250V DC | |
– resistive load | 0,3A |
– inductive load of L/R=40ms | 0,12A |
Max. breaking capacity by U=250V, 50Hz | |
– inductive load of cosϕ=0,4 | 3A |
Continuous contact carry | 5A |
Relay outputs data (S1, watchdog contact) | |
Max. breaking capacity – resistive load | |
– AC current | 6A |
– DC current | 6A/28V; 0,16A/220V |
Continuous contact carry | 5A |
Ambient temperature | (268÷313)K/(-5÷40)°C |
Relative humidity | ≤ 80% |
Ingress Protection degree | IP40 |
Weight | 0,8 kg |
Dimensions (height x width x depth) | 75 x 100 x 120 mm |
Electromagnetic compatibility according to | PN-EN 50263 |
Insulation according to | PN-EN 60255-5 |